590-Temporary Installations: Page 3 of 3

You are here

This section shall apply to power derived from an electric utility company or from an on-site-generated power source.

(A) Receptacle Outlets. All 125-volt, single-phase, 15-,

20-, and 30-ampere receptacle outlets that are not a
part of the permanent wiring of the building or
structure and that are in use by personnel shall have
ground-fault circuit-interrupter protection for
personnel. If a receptacle(s) is installed or exists as part
of the permanent wiring of the building or structure
and is used for temporary electric power, ground-fault circuit-interrupter protection for personnel shall be provided. For the purposes of this section, cord sets or devices incorporating listed ground-fault circuit- interrupter protection for personnel identified for portable use shall be permitted.

Exception: In industrial establishments only, where conditions of maintenance and supervision ensure that only qualified personnel are involved, an assured equipment grounding conductor program as specified in

590.6(B)(2) shall be permitted for only those receptacle

outlets used to supply equipment that would create a

greater hazard if power were interrupted or having a

design that is not compatible with GFCI protection.

(B) Use of Other Outlets. Receptacles other than 125- volt, single-phase, 15-, 20-, and 30-ampere receptacles shall have protection in accordance with (B)(1) or the assured equipment grounding conductor program in accordance with (B)(2).

(1) GFCI Protection. Ground-fault circuit-interrupter protection for personnel.

(2) Assured Equipment Grounding Conductor Program. A written assured equipment grounding conductor program continuously enforced at the site by one or more designated persons to ensure that equipment grounding conductors for all cord sets, receptacles that are not a part of the permanent wiring of the building or structure, and equipment connected by cord and plug are installed and maintained in accordance with the applicable requirements of 250.114, 250.138,

406.3(C), and 590.4(D).
(a) The following tests shall be performed on all cord sets, receptacles that are not part of the permanent wiring of the building or structure, and cord- and-plug-connected equipment required to be connected to an equipment grounding conductor:

(1) All equipment grounding conductors shall be tested for continuity and shall be electrically continuous.

(2) Each receptacle and attachment plug shall be tested for correct attachment of the equipment grounding conductor. The equipment grounding conductor shall be connected to its proper terminal.

(3) All required tests shall be performed as follows:

a. Before first use on site
b. When there is evidence of damage
c. Before equipment is returned to service follow ing any repairs
d. At intervals not exceeding 3 months
(b) The tests required in item (2)(a) shall be recorded and made available to the authority having jurisdiction.

590.7 Guarding. For wiring over 600 volts, nominal, suitable fencing, barriers, or other effective means shall be provided to limit access only to authorized and qualified personnel.