varying duty, as illustrated by Table 430.22(E), shall be permitted to be protected against overload by the branch-circuit short-circuit and ground-fault protective device, provided the protective device rating or setting does not exceed that specified in Table 430.52.
Any motor application shall be considered to be for continuous duty unless the nature of the apparatus it drives is such that the motor cannot operate continuously with load under any condition of use.
430.35 Shunting During Starting Period.
(A) Nonautomatically Started. For a nonautomatically started motor, the overload protection shall be permitted to be shunted or cut out of the circuit during the starting period of the motor if the device by which the overload protection is shunted or cut out cannot be left in the starting position and if fuses or inverse time circuit breakers rated or set at not over 400 percent of the full-load current of the motor are located in the circuit so as to be operative during the starting period of the motor.
(B) Automatically Started. The motor overload protec- tion shall not be shunted or cut out during the starting period if the motor is automatically started.
Exception: The motor overload protection shall be permitted to be shunted or cut out during the starting period on an automatically started motor where the following apply:
(a) The motor starting period exceeds the time delay of available motor overload protective devices, and
(b) Listed means are provided to perform the following:
(1) Sense motor rotation and automatically prevent the shunting or cutout in the event that the motor fails to start, and
(2) Limit the time of overload protection shunting or
cutout to less than the locked rotor time rating of the
protected motor, and
(3) Provide for shutdown and manual restart if motor
running condition is not reached.
430.36 Fuses — In Which Conductor. Where fuses are used for motor overload protection, a fuse shall be inserted in each ungrounded conductor and also in the grounded conductor if the supply system is 3-wire, 3-
phase ac with one conductor grounded.
430.37 Devices Other Than Fuses — In Which Conduc- tor. Where devices other than fuses are used for motor overload protection, Table 430.37 shall govern the minimum allowable number and location of overload units such as trip coils or relays.
430.38 Number of Conductors Opened by Overload Device. Motor overload devices, other than fuses or thermal protectors, shall simultaneously open a sufficient
Table 430.37 Overload Units
Number and Location of Overload Units, Such as Trip
Kind of Motor Supply System Coils or Relays
430.39 Motor Controller as Overload Protection. A mo- tor controller shall also be permitted to serve as an overload device if the number of overload units complies with Table 430.37 and if these units are operative in both the starting and running position in the case of a dc motor, and in the running position in the case of an ac motor.
430.40 Overload Relays. Overload relays and other de- vices for motor overload protection that are not capable of opening short circuits or ground