on the requirements for a motor to be classified "energy efficient," see NEMA Standards Publication No. MG1-1993, Revision, Motors and Generators, Part 12.59.
Exception No. 2: Where the motor full-load current is 8 amperes or less, the setting of the instantaneous-trip circuit breaker with a continuous current rating of 15 amperes or less in a listed combination motor controller that provides coordinated motor branch-circuit overload and short-circuit and ground-fault protection shall be permitted to be increased to the value marked on the controller.
(4) Multispeed Motor. For a multispeed motor, a single short-circuit and ground-fault protective device shall be permitted for two or more windings of the motor, provided
the rating of the protective device does not exceed the above applicable percentage of the nameplate rating of the
smallest winding protected.
Exception: For a multispeed motor, a single short-circuit and ground-fault protective device shall be permitted to be used and sized according to the full-load current of the highest current winding, where all of the following conditions are met:
(a) Each winding is equipped with individual overload protection sized according to its full-load current.
(b) The branch-circuit conductors supplying each winding are sized according to the full-load current of the highest full-load current winding.
The controller for each winding has a horsepower rating not less than that required for the winding having the highest horsepower rating.
(5) Power Electronic Devices. Suitable fuses shall be permitted in lieu of devices listed in Table 430.52 for power electronic devices in a solid-state motor controller system, provided that the marking for replacement fuses is provided adjacent to the fuses.
(6) Self-Protected Combination Controller. A listed self- protected combination controller shall be permitted in lieu of the devices specified in Table 430.52. Adjustable instantaneous-trip settings shall not exceed 1300 percent of full-load motor current for other than Design B energy-efficient motors and not more than 1700 percent of full-load motor current for Design B energy- efficient motors.
FPN: Proper application of self-protected combination controllers on 3-phase systems, other than solidly grounded wye, particularly on corner grounded delta systems, considers the self-protected combination controllers' individual pole-interrupting capability.
(7) Motor Short-Circuit Protector. A motor short-circuit protector shall be permitted in lieu of devices listed in Table 430.52 if the motor short-circuit protector is part of a listed combination motor controller having coordinated motor overload protection and short- circuit and ground-fault protection in each conductor and it will open the circuit at currents exceeding 1300
percent of motor full-load current for other than Design
B energy-efficient motors and 1700 percent of motor
full-load motor current for Design B energy-efficient
motors.
(D) Torque Motors. Torque motor branch circuits shall be protected at the motor nameplate current rating in accordance with 240.4(B).
430.53 Several Motors or Loads on One Branch Circuit. Two or more motors or one or more motors and other loads shall be permitted to be connected to the same
branch circuit under conditions specified in 430.53(D)
and in 430.53(A), (B), or (C).
(A) Not Over 1 Horsepower. Several motors, each not exceeding 1 hp in rating, shall be