due to motor overloads and failure to start by a thermal protector integral with the motor or external current-sensing devices, or both.
(2) Wound-Rotor AC Motors. The secondary circuits of wound-rotor ac motors, including conductors, controllers, and resistors rated for the application, shall be considered as protected against overcurrent by the motor overload protection means.
(3) Operation. Operation of the overload interrupting device shall simultaneously disconnect all ungrounded conductors.
(4) Automatic Reset. Overload sensing devices shall not automatically reset after trip unless resetting of the overload sensing device does not cause automatic restarting of the motor or there is no hazard to persons created by automatic restarting of the motor and its connected machinery.
(C) Fault-Current Protection.
(1) Type of Protection. Fault-current protection shall be provided in each motor circuit as specified by either (1)(a)or (l)(b).
(a) A circuit breaker of suitable type and rating ar- ranged so that it can be serviced without hazard. The circuit breaker shall simultaneously disconnect all ungrounded conductors. The circuit breaker shall be permitted to sense the fault current by means of integral or external sensing elements.
(b) Fuses of a suitable type and rating placed in each ungrounded conductor. Fuses shall be used with suitable disconnecting means, or they shall be of a type that can also serve as the disconnecting means. They shall be arranged so that they cannot be serviced while they are energized.
(2) Reclosing. Fault-current interrupting devices shall not automatically reclose the circuit.
Exception: Automatic reclosing of a circuit shall be per- mitted where the circuit is exposed to transient faults and where such automatic reclosing does not create a hazard to persons.
(3) Combination Protection. Overload protection and fault-current protection shall be permitted to be provided by the same device.
430.226 Rating of Motor Control Apparatus. The ulti- mate trip current of overcurrent (overload) relays or other motor-protective devices used shall not exceed
115 percent of the controller's continuous current rating. Where the motor branch-circuit disconnecting means is separate from the controller, the disconnecting means current rating shall not be less than the ultimate trip setting of the overcurrent relays in the circuit.
430.227 Disconnecting Means. The controller disconnecting means shall be capable of being locked in the open position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed.
XII. Protection of Live Parts — All Voltages
430.231 General. Part XII specifies that live parts shall be protected in a manner judged adequate for the hazard involved.
430.232 Where Required. Exposed live parts of motors and controllers operating at 50 volts or more between terminals shall be guarded against accidental contact by enclosure or by location as follows:
(1) By installation in a room or enclosure that is
accessible only to qualified persons
(2) By installation on a suitable balcony, gallery, or plat- form, elevated and arranged so as to exclude unqualified persons
(3) By elevation 2.5 m (8 ft)