332-Mineral Insulated Metal Sheathed Cable
additional protection is provided
I. General
332.1 Scope. This article covers the use, installation, and construction specifications for mineral-insulated, metal-sheathed cable, Type MI.
332.2 Definition.
additional protection is provided
332.1 Scope. This article covers the use, installation, and construction specifications for mineral-insulated, metal-sheathed cable, Type MI.
332.2 Definition.
the Installation of Sprinkler Systems, on all floors, ENT shall be permitted to be used within walls, floors, and ceilings, exposed or concealed, in buildings exceeding three floors abovegrade.
FPN: A finish rating is established for assemblies containing combustible (wood) supports. The finish rating is defined as the time at which the wood stud or wood joist reaches an average temperature rise of
121°C (250°F) or an individual temperature of 163°C
(325°F) as measured on the plane of the wood nearest
physical damage. Where open conductors cross ceiling joists and wall studs and are exposed to physical damage, they shall be protected by one of the following methods:
(1) Guard strips not less than 25 mm (1 in.) nominal in thickness and at least as high as the insulating supports, placed on each side of and close to the wiring.
(2) A substantial running board at least 13 mm O/2 in.)
thick in back of the conductors with side
334.1 Scope. This article covers the use, installation, and construction specifications of nonmetallic-sheathed cable.
334.2 Definitions.
installed in wet locations shall be suitable for such locations.
shall comply with this article and with the applicable pro- visions of other articles of this Code.
I. General
336.1 Scope. This article covers the use, installation, and construction specifications for power and control tray cable, Type TC.
336.2 Definition.
Power and Control Tray Cable, T>pe TC. A factory as- sembly of two or more insulated conductors, with or without associated bare or covered grounding conductors, under a nonmetallic jacket.
II. Installation
368.1 Scope. This article covers service-entrance, feeder, and branch-circuit busways and associated fittings.
368.2 Definition.
FPN: For cablebus, refer to Article 370.
402.1 Scope. This article covers general requirements and construction specifications for fixture wires.
402.2 Other Articles. Fixture wires shall comply with this article and also with the applicable provisions of other articles of this Code.
FPN: For application in luminaires, see Article 410.
338.1 Scope. This article covers the use, installation, and construction specifications of service-entrance cable.
338.2 Definitions.